Intergas Rapid 25 Plus handleiding

68 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 47 van 68
Intergas Heating Ltd 47
E
Min. supply temperature during OT
demand
(OT = OpenTherm stat)
40
40
Setting range 10°C to 60°C. If the OT thermostat
demands a supply temperature that is below this
set value, the heat demand cannot be met.
E.
OT reaction
1
1
0 = Ignore OT demand if the setpoint for the flow
temperature (value send by controller) is below
the value of par E
1 = Accept OT demand if the setpoint for the flow
temperature is below the value of par E.
The setpoint for the flow temperature is the
value of par. E
2 = Disable OT (heat demands will be accepted
with a flow temperature as set in the display)
F
Starting speed CH
60
50
Setting range 50 to 99%
F.
Starting speed DHW
60
50
Setting range 50 to 99%
H
Max. fan speed
45
45
Setting range 40 to 50 (40 = 4000 rpm, 50 = 5000
rpm) The absolute maximum speed can be set
through this parameter.
L
Legionella prevention
(only applicable when using
external tank and W-plan)
0
0
0 = Legionella prevention disabled.
1 = Legionella prevention weekly
2 = Legionella prevention daily
n
Flow temperature during heating
DHW cylinder
85
85
Setting range 60°C to 90°C
n.
Eco/Comfort DHW temperature
(keep hot facility)
0
0
Setting range 0, 40 65 °C
0 = temperature is equal to DHW temperature
setting
40 65 = absolute temperature
O.
Delay time CH
0
0
Setting range 0 = 15 minutes
o
Delay time CH after DHW
0
0
Setting range 0 15 minutes.
o.
Eco Days
3
3
Setting range : 0 10
0 = Keep hot facility controlled by Open therm
room thermostat
1 10 eco days.
P
Minimum switch off time during CH
operation
5
5
Setting range 0 to 10 minutes (anti cycling
function)
P.
DHW coefficient
30
36
Setting range 0, 24, 30, 30
0 = Applicable for combi boilers with flow switch
24 = not applicable
30 = Rapid 25
36 = Rapid 32
q
Summer mode
0
0
Not applicable
r
Heating curve coefficient
0
0
Not applicable.
9.3.1 Enable/disable keep hot facility by Open Therm room thermostat.
It is possible to enable and disable the keep hot facility of the boiler by using an Open Therm
room thermostat. For this the boiler needs to be set in Eco mode : ( LED on).
Also the parameter o. needs to be set to 0. In this setting the adaptive behaviour of the boiler
(see § 9.1.2 ) is disabled.
The Open Therm room thermostat will now enable or disable the keep hot facility (provided
that the room thermostat supports this function)