IFM VSE163 handleiding
Handleiding
Je bekijkt pagina 13 van 24

Diagnostic electronics with Modbus TCP interface VSE163
© ifm electronic gmbh 11704143 / 00 09 / 2025 13
Input (PLC)
Status Byte 1 byte Current status/state of
the object
0: OK
1: warning alarm
2: damage alarm
3: inactive
4: error
Error Word 2 bytes Error codes for descrip-
tion of error in object
state
0x0000:
no error
0x0001:
internal error
0x0002:
calculation error
0x0004:
speed out of range
0x0008:
speed not stable
0x0010:
invalid baseline
0x0020:
invalid reference value
(1)
0x0040:
invalid reference value
(2)
0x0100:
deactivated by signal
weighting
0x0200: reference value
out of range
0x1000:
warning alarm
0x3000:
warning and damage
alarm
0x8000:
object inactive (by vari-
ant)
Rotational speed • Real or DINT with factor
• Big or
Little Endian
4 bytes Trigger - rotational speed
Reference value • Real or DINT with factor
• Big or
Little Endian
4 bytes Trigger - reference value
Warning alarm • Real or DINT with factor
• Big or
Little Endian
4 bytes Limit - warning alarm (rel-
ative)
Damage alarm • Real or DINT with factor
• Big or
Little Endian
4 bytes Limit - damage alarm
(relative)
Bekijk gratis de handleiding van IFM VSE163, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
| Merk | IFM |
| Model | VSE163 |
| Categorie | Niet gecategoriseerd |
| Taal | Nederlands |
| Grootte | 1654 MB |