Diagnostic electronics with Modbus TCP interface VSE163
© ifm electronic gmbh 11704143 / 00 09 / 2025 11
Wiring of sensors 1...4 (S1...S4) according to their use
Sensor VSA IEPE/VSP 0...20 mA
S1 S2 S3 S4
09 16 20 24 BN: L+ (+ 9 V) not connected
(n.c.)
not connected
(n.c.)
10 15 19 23 WH: Signal IEPE + Signal
11 14 18 22 BU: GND IEPE - GND
12 13 17 21 BK: Test not connected
(n.c.)
not connected
(n.c.)
Sensor input Use
S1…S4 VSM
9,16,20,24 not connected (n.c.)
10,15,19,23 IEPE x IEPE y IEPE z
11,14,18,22 IEPE -
12,13,17,21 not connected (n.c.) Test *
* The self-test is only carried out via the Z axis.
Connect both cables to the same terminal of a suitable evaluation unit (e.g. VSExxx).
Terminal 1 Supply L+
When using an IEPE input 24 V + 20 % (Integrated Electronics Piezo Electric)
The ground GND of the DC supply is directly connected with the ground GND of the sensor
supply. Therefore the SELV criteria have to be met for the DC supply.
Protect the supply voltage externally (max. 2 A).
6.3 Ethernet connection
The RJ45 socket is used for the connection to the Ethernet.