4���20 mA with setting [OU2] = I or
20���4 mA with setting [OU2] = Ineg�
The measuring range is scalable:
[ASP] defines at which measured temperature value the analogue signal is
4 mA (OU2 = I) or 20 mA (OU2 = Ineg)�
[AEP] defines at which measured temperature value the analogue signal is
20 mA (OU2 = I) or 4 mA (OU2 = Ineg)�
Minimum distance between [ASP] and [AEP] = 5 K�
If the measured temperature value is outside the scaled measuring range, the
analogue signal is 20...20.5 mA or 3.8...4 mA (→ Figure 1). When the measured
temperature value continues to increase or decrease, case of diagnostic 5 occurs
(→ 5.3.3)
160
20
4
3.5
21.5
FOU = OFF
FOU = On
20.5
3.8
I [mA]
-25 0 150
MEWMAW ASP AEP
T [°C]
1
2
Figure 1: Output characteristics analogue output with factory setting
1
Setting [OU2] = I
2
Setting [OU2] = Ineg
MAW = initial value of the measuring range, MEW = final value of the measuring range,
ASP = analogue start point, AEP = analogue end point