SUH1xx SUH22x SUH3xx SUH42x SUH5xx SUH6xx SUH7xx SUH8xx Ultrasonic flow meter
26
[FOUx] Process values [SELx] Output signal Explanation
On All process values In case of an error the output goes to
21.5mA.
As soon as a defective process value
is present, the unit sets all process val-
ues to invalid.
OFF All process values In case of an error the output goes to
3.5mA.
OU Flow In case of an error the output goes to
3.5mA.
If the process value “Flow” is defective,
the unit continues to provide the pro-
cess value “Temperature”.
Temperature In case of an error the output goes to
21.5mA.
If the process value “Temperature” is
defective, the unit continues to provide
the process value “Flow”.
Frequency signal:
[FOUx] Process values [SELx] Output signal Explanation
On All process values In case of an error the output goes to
130% of [FrPx].
As soon as a defective process value
is present, the device sets all process
values to invalid.
OFF All process values In case of an error the output goes to
0Hz.
OU Flow In case of an error the output goes to
0Hz.
If the process value “Flow” is defective,
the device continues to provide the
process value “Temperature”.
Temperature In case of an error the output goes to
130% of [FrPx].
If the process value “Temperature” is
defective, the device continues to pro-
vide the process value “Flow”.
The parameter [FOU] has no influence on the pulse signal, the diagnostic signals for flow
direction and signal quality and the IO-Link process data transmission.
9.2.7 Output off
The output signal can be switched off via the parameter [oux] = [OFF]. The output then goes to high
impedance.
Communication via the IO-Link interface on OUT1 remains active.
9.3 Application configuration
The chapter describes the setting options for adaptation to your specific application.
9.3.1 Standard unit of measurement
It is possible to set a unit of measurement for each process value, on which further parameter settings
will be based.
Selectable values:
Flow [uni.F]:
SUHxx0: l/min; l/h; m
3
/h; m/s.
SUHxx1: l/min; l/h; m
3
/h; m/s; gal/min; gal/h; ft/s; oz/min.
Temperature [uni.T]:
SUHxx0: °C.
SUHxx1: °C; °F.
9.3.2 Process value for OUT1 and OUT2
The process value to be output via OUTx can be selected using the parameter [SELx].