Ultrasonic flow meter SUH1xx SUH22x SUH3xx SUH42x SUH5xx SUH6xx SUH7xx SUH8xx
25
Frequency signal for temperature:
FOU = OFF 0
FOU = ON 130
120
100
UL
Err
Err
= FrPx
MAW
FSPx
FEPx MEW
OL
100 120
[% MEW]
[% FrPx]
3
2
1
B
A
Fig.13: Output characteristic of the frequency output, temperature
A: Frequency signal MAW: Initial value of the measuring range
B: Temperature MEW: Final value of the measuring range
1: Indicating range FSPx: Frequency start point
2: Measuring range FEPx: Frequency end point
3: Scaled measuring range FrPx: Frequency signal (Hz) for upper measured value
Err: Error OL: Above the indicating range
UL: Below the indicating range
Parameters to be set:
[ou1] = [FRQ]; [FrP1]; [FSP1] (only for TEMP); [FEP1]
9.2.6 Error behaviour of the outputs
The response of the OUTx output in case of a fault can be set via the parameter [FOUx]. Depending
on the selected output function, the following signals are provided in case of a fault:
Switching signal:
[FOUx] Process values [SELx] Output signal Explanation
On All process values The output switches ON in case of a
fault.
As soon as a defective process value
is present, the device sets all process
values to invalid.
OFF All process values The output switches OFF in case of a
fault.
OU Flow The output switches OFF in case of a
fault.
If the process value “Flow” is defective,
the device continues to provide the
process value “Temperature”.
Temperature The output switches ON in case of a
fault.
If the process value “Temperature” is
defective, the device continues to pro-
vide the process value “Flow”.
Analogue signal: