Ultrasonic flow meter SUH1xx SUH22x SUH3xx SUH42x SUH5xx SUH6xx SUH7xx SUH8xx
23
MEWMAW AEPASP
-120Q [% MEW]
[°C]T -48 -40 120 144 156
-130
-52
[°F]-54,4 -40 248 291,2 312,8-61,6
120100-100 130
4
3,8
3,5FOU=OFF
20
20,5
21,5
[mA]
FOU=On
cr.UL UL OL cr.OL
2
3
4
1
B
A
Fig.11: Characteristic of the analogue output according to IEC 60947-5-7.
A: Analogue signal MAW: Initial value of the measuring range
B: Process value MEW: Final value of the measuring range
1: Detection range ASP: Analogue start point
2: Display range AEP: Analogue end point
3: Measuring range UL: Below the display range
4: Scaled measuring range cr.UL: Below the detection range
Q: Flow OL: Above the display range
T: Temperature cr.OL: Above the detection range
The analogue signal in case of a fault can be set via the parameter [FOU]: Error behaviour of
the outputs (Ò/25).
Parameters to be set:
[ou2] = [I/4…20mA], [ASP2]; [AEP2]
9.2.5 Frequency signal
The device provides a frequency signal proportional to the process value.
The frequency signal is adjustable:
[FrP1] defines the frequency signal in Hz that is provided when the upper measured value is
reached.
Setting range: 1 Hz…10 kHz.
The measuring range is scalable:
[FSP1] defines the lower measured value from which a frequency signal is provided.