Ultrasonic flow meter without display SUHxxx
© ifm electronic gmbh 11661449 / 01 07 / 2025 19
9 Set-up
After power on and expiry of the power-on delay time, the unit is in the normal operating mode. It carries
out its measurement and evaluation functions and generates output signals according to the set
parameters.
During the power-on delay time, the outputs are in the following status according to the set parameters:
ON with normally open function (Hno / Fno)
OFF with normally closed function (Hnc / Fnc)
ON for detection of direction (dir.F)
OFF for frequency output (FRQ)
OFF for consumed quantity monitoring (ImP)
20 mA for current output (I)
When an IO-Link master is connected, the device automatically goes from SIO mode (standard
input-output) into IO-Link mode if the port of the master is set to IO-Link mode.