Ultrasonic flow meter SUH1xx SUH22x SUH3xx SUH42x SUH5xx SUH6xx SUH7xx SUH8xx
17
9 Parameter setting
Parameters can be set before installation or during operation.
If you change parameters during operation, this will influence the function of the plant.
u Ensure that there will be no malfunctions in your plant.
During parameter setting the unit remains in the operating mode. It continues to monitor with the
existing parameter until the parameter setting has been completed.
The device parameters can be set via the IO-Link interface in the following ways, for example:
Parameter setting via a suitable parameter setting software, e.g. ifm moneo|configure
Parameter setting via a PLC
Parameter setting via an IIoT application
Requirements for parameter setting via the IO-Link interface:
ü The Input Output Device Description (IODD) for the device in case of parameter setting via a
parameter setting software, see documentation.ifm.com
ü The IO-Link interface description (PDF) for the device in case of parameter setting via a PLC or
IIoT application, see documentation.ifm.com
ü An IO-Link master
u Connect the IO-Link master to the parameter setting software, the PLC or the IIoT application.
u Connect the device to a suitable free port of the IO-Link master.
u Set the port of the IO-Link master to the IO-Link operating mode.
w The device changes to the IO-Link mode.
u Change the parameter settings in the software.
u Write the parameter settings to the device.
Support for system integration and parameter setting via IO-Link:
Ò Manual of the parameter setting software (e.g. moneo)
Ò Explanations and startup packages at ifm.com/cnt/io-link-system-integration.
9.1 Adjustable parameters
Parameter Explanation
AEP2 Analogue end point for OUT2 = process value at which the output signal is 20mA.
ASP2 Analogue start point for OUT2 = process value at which the output signal is 4mA.
APPL Application reset (reset of application-specific parameter settings)
BtB Back-to-Box reset (reset to factory settings)
CGA Calibration factor in % for adapting the measured value curve to the application
coF Correction factor for zero point calibration
dAP.F Damping constant in seconds for flow (63 % rise time τ)
dFUx Switching signal for diagnostic output OUTx: direction of flow (Fdir) or signal quality (Sig.Q)
DIn2 Reset signal for external totaliser reset
Fdir Direction of flow
FEP1 Frequency end point for OUT1 = Upper measured value at which the frequency signal set under
FrP1 is provided.
FHx Upper limit for switching signal OUTx with window function
FLx Lower limit for switching signal OUTx with window function