IFM SU7050 handleiding
Handleiding
Je bekijkt pagina 15 van 38

Ultrasonic flow meter SU2x5x SU6x5x SU7x5x SU8x5x SU9x5x
15
8 Set-up
After power on and expiry of the power-on delay time, the unit is in the normal operating mode. It
carries out its measurement and evaluation functions and generates output signals according to the
set parameters.
During the power-on delay time, the outputs are in the following status according to the set
parameters:
• ON with normally open function (Hno / Fno)
• OFF with normally closed function (Hnc / Fnc)
• ON for detection of direction (F.Dir)
• OFF for frequency output (FRQ)
• OFF for consumed quantity monitoring (ImP)
• 20 mA for current output (I)
• 10 V for voltage output (U = 0…10V)
• 4.5 V for voltage output (U = 0.5…4.5V)
Bekijk gratis de handleiding van IFM SU7050, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
| Merk | IFM |
| Model | SU7050 |
| Categorie | Niet gecategoriseerd |
| Taal | Nederlands |
| Grootte | 2887 MB |







