Ultrasonic flow meter SU2x5x SU6x5x SU7x5x SU8x5x SU9x5x
15
8 Set-up
After power on and expiry of the power-on delay time, the unit is in the normal operating mode. It
carries out its measurement and evaluation functions and generates output signals according to the
set parameters.
During the power-on delay time, the outputs are in the following status according to the set
parameters:
ON with normally open function (Hno / Fno)
OFF with normally closed function (Hnc / Fnc)
ON for detection of direction (F.Dir)
OFF for frequency output (FRQ)
OFF for consumed quantity monitoring (ImP)
20 mA for current output (I)
10 V for voltage output (U = 0…10V)
4.5 V for voltage output (U = 0.5…4.5V)