IO-Link event
Name / Code
Problem Corrective measures
No media detected
0x8CC5
36037d
No medium present or signal quality too low
due to interference in the pipe length.
u Check whether medium is present in
the sensor tube.
u Remove the device and check for
deposits.
u Check application for interference (air
bubbles/particles).
Parameter error
0x6320
25376d
Parameter setting outside the valid range.
u Check parameter setting.
u Perform a back-to-box reset.
Measuring range exceeded
0x8C20
35872d
Above the detection range (cr.OL).
u Check the measuring range.
Measuring range exceeded
0x8C20
35872d
Below the detection range (cr.UL).
u Check the measuring range.
In the event of an error, the outputs react according to the setting under [FOU].