Electronic pressure sensor PY1705 PY1707 PY1709 PY1717 PY1718 PY1726 PY1728 PY1789
11
Zero point behaviour of the device display and switching output:
5
4
1
0
0
5
+
+
-
2
3
Fig.2: Device display and switching output
1: Process value
2: Sensor output signal with hysteresis (green)
3: Ideal measurement signal (red)
4: System pressure
5:
Zero point stabilisation Ò Data sheet
The first process value that is shown on the device display and can be evaluated via the switching
output is determined by the zero point stabilisation.
The switching output cannot be configured within the zero point stabilisation.
The zero point stabilisation is specified in % of the span Ò Data sheet.
Zero point behaviour of the analogue output and communication via IO-Link:
5
4
3
1
0
0
5
-
+
+
2
6
6
Fig.3: Analogue output and communication via IO-Link
1: Process value
2: Sensor output signal (green)
3: Ideal measurement signal (red)
4: System pressure
5:
Zero point stabilisation Ò Data sheet
6:
0.5 x zero point stabilisation Ò data sheet
The first process value that can be evaluated via the analogue output and the IO-Link communication
is indicated by the half zero point stabilisation (6).
In the further range of the zero point stabilisation (5), the output signal of the sensor runs at a larger
gradient angle.
The zero point stabilisation is specified in % of the span Ò Data sheet.
4.6 Operating modes
The operating mode is defined by the wiring (Ò Electrical connection) and automatically recognised by
the unit.
4.6.1 2-wire operation
OUT2 (pin 2) Analogue signal proportional to pressure 4…20 mA or 20...4 mA