Current output 4...20 mA
Factory setting Measuring range scaled










P =
MEW =
ASP =
AEP=
system pressure
final value of the measuring range
analogue start point [ASP2]
analogue end point [AEP2]
In the measuring range of the corresponding unit the output signal is between 4 and
20 mA�
It is also indicated:
• System pressure above [AEP2]: 20���20�5 mA
• System pressure below [ASP2]: 4���3�8 mA
• Fault indication according to Namur: 21�5 mA
4.5 IO-Link
4.5.1 General information
The device has an IO-Link communication interface which requires an IO-Link-
capable module (IO-Link master) for operation�
The IO-Link interface enables direct access to the process and diagnostic data
and provides the possibility to set the parameters of the unit during operation�
In addition, communication is possible via a point-to-point connection with a USB
adapter cable�
The IODDs necessary for the configuration of the unit, detailed information about
process data structure, diagnostic information, parameter addresses and the
necessary information about the required IO-Link hardware and software can be
found at www�ifm�com�