IFM PN2696 handleiding
Handleiding
Je bekijkt pagina 7 van 33

7
UK
4.2 Communication, parameter setting, evaluation
OUT1 (pin 4)
• Switching signal for system pressure limit
• Communication via IO-Link
OUT2 (pin 2)
• Switching signal for system pressure limit
• Analogue signal 4���20 mA / 0���10 V
4.3 Switching function
OUTx changes its switching status if it is above or below the set switching limits
(SPx, rPx)� The following switching functions can be selected:
• Hysteresis function / normally open: [ou1/ou2] = [Hno] (→ Fig. 1).
• Hysteresis function / normally closed: [ou1/ou2] = [Hnc] (→ Fig. 1).
First the set point (SPx) is set, then the reset point (rPx)�
The hysteresis defined remains even if SPx is changed again�
• Window function / normally open: [ou1/ou2] = [Fno] (→ Fig. 2).
• Window function / normally closed: [ou1/ou2] = [Fnc] (→ Fig. 2).
The width of the window can be set by means of the difference between FHx
and FLx� FHx = upper value, FLx = lower value�
FH
FL
1 2
P = system pressure; HY = hysteresis; FE = window
When set to the window function the set and reset points have a fixed
hysteresis of 0�25 % of the measuring span�
Bekijk gratis de handleiding van IFM PN2696, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.