Electronic manometer PG17xx
25
Output configuration [OU2]menu:
BACk
[EF]
OU1
CFG
OU2
DIS
DIA
SIM
RES
tASP
ASP2
tAEP
AEP2
dAA
ou2
BACk
[OU2]
----
----
----
YES│no
I │InEG│OFF
YES│no
On│OFF
FOU2
Main menu
Parameter Explanation
ou2 Output function for OUT2 (analogue signal)
tASP Teach analogue start point ASP2
ASP2 Analogue start point for OUT2 = process value at which the output signal is 4 mA (for ou2 = Ineg:
20 mA).
tAEP Teach analogue end point AEP2
AEP2 Analogue end point for OUT2 = process value at which the output signal is 20 mA (for ou2 = Ineg:
4 mA).
dAA Damping time in seconds for the analogue signal
FOU2 Behaviour of output OUT2 in case of error