IFM PG1708 handleiding
Handleiding
Je bekijkt pagina 24 van 55

PG17xx Electronic manometer
24
Output configuration [OU1]menu:
BACk
[EF]
OU1
CFG
OU2
DIS
DIA
SIM
RES
LoGc
ModE
tSP1
SP1
tSP2
ou1
SP2
HYSt
dS
dr
BACk
[OU1]
SSC1│OFF
H.Act│L.Act
YES│no
2-P│WInd│1-P│DEac
----
YES│no
----
----
----
----
On│OFF
FOU1
Main menu
Parameter Explanation
ou1 Output function for output OUT1: [SSC1] = switching signal with parameter settings for SSC1.1;
[OFF].
LoGc Switch-point logic: [H.Act] = high active or [L.Act] = low active
ModE Switch point mode: [1-P] = single point mode; [2-P] = two point mode; [WInd] = window mode; [De-
ac] = deactivated.
tSP1 Teach switch point SP1
SP1 Switch point 1
tSP2 Teach switch point SP2
SP2 Switch point 2
HYSt Hysteresis
dS Switching delay for change into active state (in seconds)
dr Switch-off delay for change into inactive state (in seconds)
FOU1 Behaviour of output OUT1 in case of an error