IFM PG1707 handleiding
Handleiding
Je bekijkt pagina 31 van 55

Electronic manometer PG17xx
31
• [Two Point Mode]
• [Window Mode]
The switching signal channel changes to the active state depending on the process data value (PDV).
The active state is above the switch point in [Single Point Mode] and [Two Point Mode] and within the
window section in [Window Mode].
Switch point logic
By setting the switch point logic [High active] or [Low active], you can specify which value the
switching signal channel has in the active state:
• [High active]: The switching signal channel is “high” in the active state (= ON = normally open = 1)
• [Low active]: The switching signal channel is “low” in the active state (= OFF = normally closed = 0)
The following figures show the status of the switching signal channels depending on the switch point
mode, switch point logic and process data value (PDV).
Deactivated
If the [Deactivated] switch point mode is set for a switching signal channel, then the switching signal
channel will permanently have the following value regardless of the process value:
• For switch point logic [High active]: permanently “low”.
• For switch point logic [Low active]: permanently “high”.
low
PDV
0
Fig.11: [Deactivated] / [High active]
high
PDV
1
Fig.12: [Deactivated] / [Low active]
Single Point Mode
Only one switch point (SP1) is manually set or taught.
The reset point (SP1-H) results from the switch point and the set hysteresis.
When teaching, the switch point is set below the taught process value (TP1) by the hysteresis.
SP1
low
high
TP1
PDV
0
1
H
H
SP1
-
H TP1
-
H
Fig.13: [Single Point Mode] / [High active]
H: Hysteresis
SP1: Switch point
TP1: Teach point
TP1-H: Switch point during teach (= SP1)
SP1-H Reset point
SP1
low
high
TP1
PDV
1
0
H
H
SP1
-
H TP1
-
H
Fig.14: [Single Point Mode] / [Low active]
H: Hysteresis
SP1: Switch point
TP1: Teach point
TP1-H: Switch point during teach (= SP1)
SP1-H Reset point
Two Point Mode
One switch point SP1 and one switch point SP2 are manually set or taught.