Electronic sensor for level and temperature LT39xx
33
10.5 Error indications
Indication Possible cause Recommended actions
[Err] Fault in the electronics.
u Replace the unit.
[SEnS] Interfering sources (e.g. EMC)
Faulty wiring
Supply voltage disturbed
u Check electrical connection.
u Check connection between the sensor and the tank
ground.
[FAIL] Error during adjustment of the overflow prevention
OP:
Overflow prevention covered by the medium
during adjustment.
Overflow prevention soiled.
Minimum distances too small.
Mounting element detected below the overflow
prevention.
Measured value not constant.
u Lower the level, if possible.
u Clean the probe.
u Observe the notes on installation.
u Correct the position of the overflow prevention OP.
u Repeat the adjustment.
u Deactivate OP.
[cr.UL] Error: temperature below approx. -40°C.
u Check process temperature and correct, if
necessary.
[cr.OL] Error: temperature exceeding approx. +125°C.
u Check process temperature and correct, if
necessary.
[SC1] + LED 8 Flashing: Short circuit in switching output OUT1.
u Remove the short circuit.
[PArA] Faulty data set.
u Reset to factory settings [rES].
10.6 Output response in different operating states
OUT1 OUT2*
Initialisation phase OFF 0 mA
Overflow prevention OP not
adjusted.
OFF 3.5 mA
Overflow prevention OP ad-
justed or deactivated, nor-
mal operation,
according to process value and
[ou1] setting
according to process value
4...20 mA
Fault OFF for [FOU1] = [OFF]
ON for [FOU1] = [On]
<3.6mA at [FOU2] = [OFF]
>21mA at [FOU2] = [On]
* If the output function [ou2] = [I] has been selected.