Electronic sensor for level and temperature LT39xx
15
More information [OP]: Ò calculation aids [OP]
5.2 Installation instructions for the operation without overflow
prevention
u [MEdI] = [Auto] or [OP] = [OFF] (overflow prevention OP deactivated!)
5.2.1 Installation in the inactive zone
Between the maximum level (b1) and the inactive zone (I1), the minimum distance (a1) has to
be adhered to!
A I1
c
I2
b1 a1
x
u
u Fix the unit using mounting elements in the inactive zone (I1).
The outside length (c) must not exceed (I1) (Ò Table).
u Ensure that the maximum level (b1) is not exceeded after
completed installation (Ò Table).
u Further minimum distances must be adhered to: Installation in
the active zone (Ò/15)
I1 / I2: Inactive zones
A: Active zone
a1: Minimum distance between the inactive zone (I1) and the maximum level (b1)
b1: Max. level from the lower edge of the sensor (without offset)
c: Outside length
LTx922 LTx923 LTx924
[cm] [cm] [cm]
I1 5.3 6.0 10.4
A 19.5 39.0 58.5
a1 1.0 1.5 2.5
b1 20.0 39.5 59.5
5.2.2 Installation in the active zone
Between the maximum level (b2) and the mounting element a minimum distance (a2) has to be
observed!