IFM LT3923 handleiding

36 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 15 van 36
Electronic sensor for level and temperature LT39xx
15
More information [OP]: Ò calculation aids [OP]
5.2 Installation instructions for the operation without overflow
prevention
u [MEdI] = [Auto] or [OP] = [OFF] (overflow prevention OP deactivated!)
5.2.1 Installation in the inactive zone
Between the maximum level (b1) and the inactive zone (I1), the minimum distance (a1) has to
be adhered to!
A I1
c
I2
b1 a1
x
u
u Fix the unit using mounting elements in the inactive zone (I1).
The outside length (c) must not exceed (I1) (Ò Table).
u Ensure that the maximum level (b1) is not exceeded after
completed installation (Ò Table).
u Further minimum distances must be adhered to: Installation in
the active zone (Ò/15)
I1 / I2: Inactive zones
A: Active zone
a1: Minimum distance between the inactive zone (I1) and the maximum level (b1)
b1: Max. level from the lower edge of the sensor (without offset)
c: Outside length
LTx922 LTx923 LTx924
[cm] [cm] [cm]
I1 5.3 6.0 10.4
A 19.5 39.0 58.5
a1 1.0 1.5 2.5
b1 20.0 39.5 59.5
5.2.2 Installation in the active zone
Between the maximum level (b2) and the mounting element a minimum distance (a2) has to be
observed!

Bekijk gratis de handleiding van IFM LT3923, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkIFM
ModelLT3923
CategorieNiet gecategoriseerd
TaalNederlands
Grootte2799 MB