Electronic sensor for level and temperature LT39xx
31
9.7.5.1 Definition"from the cover"
OP
c
z
B
L
Required distance (y) of the overflow prevention OP "from the
cover" is defined.
Without offset ([OFS] = [0]):
[OP] = L - c - y
With offset ([OFS] = u):
[OP]=L-c-y+u
or
[OP]=B-y
Example LTx922:
c = 3.0 cm, y = 5.0 cm, u = 1.0 cm
Without offset:
[OP] = 26.4 cm - 3.0 cm - 5.0 cm = 18.4 cm
With offset:
[OP] = 26.4 cm - 3.0 cm - 5.0 cm + 1.0 cm= 19.4 cm
9.7.5.2 Definition"from the bottom"
Response level (z) of the overflow prevention OP from the tank bottom is defined.
Without offset ([OFS] = [0]): [OP] = z - u
With offset ([OFS] = u): [OP] = z
Example LTx922:
z=18.0cm (from the tank bottom), u=1.0cm
Without offset: [OP] = 18.0cm-1.0cm =17.0cm
With offset: [OP]=18.0cm
u Round the calculated value to the next lower adjustable value: Ò Setting values for [OP].
9.7.6 Setting ranges [ASP2] and [AEP2]
[°C]
min max
[ASP2] -20 68
[AEP2] 2 90
Step increment 0.5