LT39xx Electronic sensor for level and temperature
18
6 Electrical connection
The unit must be connected by a qualified electrician.
The national and international regulations for the installation of electrical equipment must be
adhered to.
Supply voltage SELV, PELV according to the technical data sheet.
u Disconnect power.
u Connect the unit as follows:
L
1 BN
2 WH
4 BK
3 BU
OUT1/IO-Link
OUT2
L+
43
2 1
Pin Core colour
1: BN Brown
2: WH White
3: BU Blue
4: BK Black
OUT1:
• Switching output
• IO-Link
OUT2:
• Analogue output
Colours to DIN EN 60947-5-2
u For safe function, the sensor housing must be electrically
connected to the counter-electrode (grounding).
u Use the housing connection (see drawing) and a short
piece of cable with a wire cross-section of at least
1.5mm
2
.
u For plastic tanks, a counter-electrode must be provided,
e.g. a metal plate inside the tank in parallel with the probe.
Adhere to minimum distances to the probe.
When using metal tanks, the tank wall serves as the counter-electrode.
Circuit examples:
2
1
L
1
BN
4
BK
2
WH
3
BU
L+
L
1
BN
2
WH
4
BK
3
BU
L+
1: 1x positive switching / 1 x analogue
2: 1x negative switching / 1 x analogue