LT39xx Electronic sensor for level and temperature
14
5 Installation
OP
c
L: Probe length u...y: Minimum distances
M: Zone for mounting element OP: Overflow prevention
c: Max. outside length B: Metal object inside the tank
LT3922 LT3923 LT3924
[cm] [cm] [cm]
L (rod length) 26.4 47.2 72.8
M (mounting zone) 14.0 23.0 36.0
c (max. outside length)*
* Applies to the installation as shown (the wall thickness of the tank lid was neglected; the mounting
element does not protrude inside the tank).
u Otherwise: note mounting zone M.
5.1 Notes on installation instructions for the operation with
overflow prevention
u [MEdI] = [CLW..] or [OIL..]
u [OP] = [value ...] (Overflow prevention OP activated!)
It is permitted to fix the mounting elements within the mounting zone (M) (Ò Installation).
u Adhere to the maximum permitted outside length (c) (Ò Installation).
u Observe minimum distances (Ò Installation).
u Observe the notes on the integrated overflow prevention OP.
The overflow prevention OP must:
1. be below the mounting element
2. be set at a minimum distance (y) to it. The minimum distance is measured between the lower
edge of the mounting element and the OP value.
MEdI = CLW.1 MEdI = CLW.2, OIL.1 MEdI = OIL.2
[cm] [cm] [cm]
x 2.0 3.0 4.0
u 1.0 1.0 1.0
y (LTx922) 2.5 3.5 4.5
y (LTx923) 4.5 5.5 6.5
y (LTx924) 6.0 7.0 8.0
v 4.5 4.5 4.5
w 4.0 5.0 6.0