E11775 E11847 ProcessLine module
8
5 Electrical connection
The unit must be connected by a qualified electrician.
u Observe the national and international regulations for the installation of electrical equipment.
The AS-i / AUX circuits are insulated from each other and from device surfaces that could be touched
with basic insulation according to IEC 61010-1 (secondary circuit with max. 32 V DC, supplied from
the mains circuit up to 300 V of overvoltage category II).
M12 socket
3
1 2
4
5
Pin
1 AS-i +
2 AUX +
3 AS-i -
4 AUX -
5 Functional earth FE
E11775
Cable: 10 m, PUR / PVC, black, Ø 11 mm; 3 x 0.75 mm² + 16 x 0.34 mm²
E11847
Cable: 25 m, PUR / PVC, black, Ø 11 mm; 3 x 0.75 mm² + 16 x 0.34 mm²
Observe the maximum current rating of the M12 connections (→ tech. data).
ATTENTION
No current limitation in the device.
w If the M12 connectors are overloaded (overcurrent), damage to the device or fire is
possible.
w Each power supply connection AS-i + / AUX + must be limited by external measures to
the values specified in the technical data (current consumption).
u Device protected.