IFM DW3003 handleiding
Handleiding
Je bekijkt pagina 19 van 32

Evaluation unit for monitoring and converting frequency signals DW3003
19
7.3 Display of error messages
SC-1
1
Fig.15: Display of error messages
1: Display of error messages
If an event such as a short circuit at output 1 is triggered, it will be displayed instead of the process
data.
What the different events mean is described under Troubleshooting (Ò/31).
7.4 LEDs
LED Function Colour State Description
Status Status Green Off Device switched off.
On Device ready for operation.
Double flashing IO-Link localisation.
Red On Device hardware fault.
Flashing Malfunction due to external factors
Ò IO-Link events or display.
Input 1 Pulse input 1 Yellow Off Input inactive.
On Input active.
Double flashing IO-Link localisation.
Restart 1 Restart input 1 Yellow Off Input inactive.
On Input active.
Double flashing IO-Link localisation.
Reset 1/2 Reset input 1/2 Yellow Off Input inactive.
On Input.
Double flashing IO-Link localisation.
IO-Link Green Off No IO-Link communication.
On IO-Link communication.
Double flashing IO-Link localisation.
Output 1 Digital output 1 Yellow Off Output inactive.
On Output active.
Flashing with 4 Hz Short circuit.
Double flashing IO-Link localisation.
Output 2 Digital output 2 Yellow Off Output inactive.
On Output active.
Flashing with 4 Hz Short circuit.
Double flashing IO-Link localisation.
Error signals and diagnostics under Troubleshooting (Ò/31).
Bekijk gratis de handleiding van IFM DW3003, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
| Merk | IFM |
| Model | DW3003 |
| Categorie | Niet gecategoriseerd |
| Taal | Nederlands |
| Grootte | 2679 MB |







