Evaluation unit for monitoring and converting frequency signals DW3003
19
7.3 Display of error messages
SC-1
1
Fig.15: Display of error messages
1: Display of error messages
If an event such as a short circuit at output 1 is triggered, it will be displayed instead of the process
data.
What the different events mean is described under Troubleshooting (Ò/31).
7.4 LEDs
LED Function Colour State Description
Status Status Green Off Device switched off.
On Device ready for operation.
Double flashing IO-Link localisation.
Red On Device hardware fault.
Flashing Malfunction due to external factors
Ò IO-Link events or display.
Input 1 Pulse input 1 Yellow Off Input inactive.
On Input active.
Double flashing IO-Link localisation.
Restart 1 Restart input 1 Yellow Off Input inactive.
On Input active.
Double flashing IO-Link localisation.
Reset 1/2 Reset input 1/2 Yellow Off Input inactive.
On Input.
Double flashing IO-Link localisation.
IO-Link Green Off No IO-Link communication.
On IO-Link communication.
Double flashing IO-Link localisation.
Output 1 Digital output 1 Yellow Off Output inactive.
On Output active.
Flashing with 4 Hz Short circuit.
Double flashing IO-Link localisation.
Output 2 Digital output 2 Yellow Off Output inactive.
On Output active.
Flashing with 4 Hz Short circuit.
Double flashing IO-Link localisation.
Error signals and diagnostics under Troubleshooting (Ò/31).