Evaluation unit for monitoring and converting frequency signals DW3003
11
5 Installation
u Disconnect power.
To ensure correct operation, install the device in a housing that can only be opened using a tool or in a
locked control cabinet (both protection rating IP 54 or higher) as an enclosure in accordance with
EN61010-1.
u Install the device vertically on a 35 mm DIN rail.
u Leave enough space (≥ 50 mm) between the device and the top and bottom of the control cabinet
to enable air circulation and to avoid excessive heating.
ATTENTION
If units are mounted side by side, inadmissible heating may occur between the units.
w Malfunction / damage is possible.
u Take into account the internal heating of all devices when mounting different devices
side by side and observe the environmental conditions for each device.