IFM AL4302 handleiding

83 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 62 van 83
AL4302 Remote I/O module 8DO 8DI
62
11 Appendix
11.1 PROFINET
11.1.1 Parameters
11.1.1.1 Modules: 8DO / 8DI modules
Submodule: 8DO/8DI + qualifier
Per input channel:
Parameter Description Values Access
Debounce Time
[*0.1ms]
Debounce time (value * 0.1ms) 0: 0ms (default)
500: 50 ms
rw
1
Hold time [*0.1ms] Hold time (value * 0.1ms) 0: 0ms (default)
60000: 6000 ms
rw
1
Hold level Hold level 0: Low: hold LOW
1: High: hold HIGH (default)
rw
1
Input Inverter Signal inversion 0: Signal not inverted: do not invert signal
(default)
1: Signal inverted: signal inversion
rw
1
1
Read and write
Per output channel:
Parameter Description Value range Access
Digital Output Current
Limit
Max. current value of the digital output
(value in mA)
0: 0mA
2000: 2000mA (default)
3600: 3600mA
rw
1
Digital Output State
Communication Lost
Fall-back value if the connection to the
controller is interrupted
Set OFF when communication lost: OFF
state (default)
Set ON when communication lost: ON
state
Keep last value when communication lost:
keep last valid state
rw
1
Digital Output Select Control instance for digital output PLC: fieldbus control (default)
MAIN SSC 1: switching channel main
counter 1
BATCH SSC 1: switching channel batch
counter 1
MAIN SSC 2: switching channel main
counter 2
BATCH SSC 2: switching channel batch
counter 2
MAIN SSC 3: switching channel main
counter 3
BATCH SSC 3: switching channel batch
counter 3
MAIN SSC 4: switching channel main
counter 4
BATCH SSC 4: switching channel batch
counter 4
rw
1

Bekijk gratis de handleiding van IFM AL4302, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkIFM
ModelAL4302
CategorieNiet gecategoriseerd
TaalNederlands
Grootte7072 MB