IFM AL4242 handleiding

82 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 63 van 82
Remote I/O module 8DO 8DI AL4242
63
Mapping: Counter Configuration
Register
Bit
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
n Counter Mode
n+1 Pin 2 Function
n+2 Counter Direction Select
n+3 Main Threshold (Word 0)
n+4 Main Threshold (Word 1)
n+5 Batch Threshold
n+6 Force Main Counter (Word 0)
n+7 Force Main Counter (Word 1)
n+8 Force Batch Counter
Legend:
Counter Mode Operating mode of the counter
module
1WORD /
rw
0x0000: CTU -up counter (default)
0x0001:CTD – down counter
0x0002: CTUD – up and down counter
0x0003: CTDIR – up or down counter
Pin 2 Function Pin 2 function of the port 1WORD /
rw
0x0000: N/C -no function (default)
0x0001: counter edge input 2 – counting
input
0x0002: count direction – select counting
direction
0x0003: reset main + batch counter - reset
counter module
0x0004: Disable main + batch counter –
disable counter module
Counter Direction Select Instance for selecting the count-
ing direction
1WORD /
rw
0x0000: pin 2 (default)
0x0001: PLC
Main Threshold Threshold CT of the main coun-
ter
MainThreshold = 0x01234567
MainThreshold[0] = 0x0123
MainThreshold[1] = 0x4567
2WORD /
rw
0x00000001: 1
0xFFFFFFFF: 4294967295 (default)
Batch Threshold Threshold CTb of the batch
counter
1WORD /
rw
0x0001: 1
0xFFFF: 65535 (default)
Force Main Counter Set counter value of the main
counter
ForceMainCounter =
0x01234567
ForceMainCounter[0] =
0x0123
ForceMainCounter[1] =
0x4567
2WORD /
rw
0x00000000: 0 (default)
0xFFFFFFFE: 4294967294
Force Batch Counter Set counter value of the batch
counter
1WORD /
rw
0x0000: 0 (default)
0xFFFE: 65534

Bekijk gratis de handleiding van IFM AL4242, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.