IFM AL4222 handleiding

88 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 17 van 88
Remote I/O module 8DO 8DI AL4222
17
0
1
SSC
1 1
0
1
SSC
0
1
SSC
1
2
1
2
SP1
SP2
Main
Batch
t
Fig.15: Window mode (high-active) with switch delay (1)
and reset delay (2)
0
1
SSC
1 1
0
1
SSC
0
1
SSC
1
2
1
2
SP1
SP2
Main
Batch
t
Fig.16: Window mode (low-active) with switch delay (1) and
reset delay (2)
Using the hysteresis function, the switching thresholds of switch points SP1 and SP2 can be equally
increased or decreased.
Switching:
Increasing counter value reaches SP2
Decreasing counter value reaches SP1
Switching back:
Increasing counter value reaches SP1 + HyS
if SP1 + HyS > HyS
max
, then reset at HyS
max
Decreasing counter value reaches SP2 - HyS
If SP2 – HyS < 0, then reset at 0
0
1
SSC
0
1
SSC
1
2
1
2
0
1
SSC
SP1
SP2
Main
Batch
t
HyS
HyS
Fig.17: Window mode (high-active) with hysteresis
0
1
SSC
0
1
SSC
1
2
1
2
0
1
SSC
SP1
SP2
Main
Batch
t
HyS
HyS
Fig.18: Window mode (low-active) with hysteresis
4.8 EtherNet/IP
The unit supports the following EtherNet/IP functions:
Device type: EtherNet/IP adapter
Device Level Ring (DLR) - Media Redundancy
Address Conflict Detection (ACD)
Quality of Service (QoS)