IFM AL4203 handleiding
Handleiding
Je bekijkt pagina 30 van 82

AL4203 Remote I/O module 8DO 8DI
30
ü The detailed view of the device is active.
u Select menu [io] > [port[n]] > [ssc] (n: 5...8).
w The menu page shows the current settings of the switching channels of the main counter (main)
and the batch counter (batch) of the port.
u Set the parameters.
u Write the changed values to the device.
w The switching signal channels are configured.
9.1.4.4 Configuring outputs
Available parameters:
Parameter Description Value range Access
[current_limit] Max. output current of the digital out-
put (value in mA)
• 0: 0 A
…
• 1000: 1000mA (default)
…
• 3600: 3600mA
rw
1
[output_select] Selection of control instance of digital
output
• PLC: higher-level PLC
• Counter 1 SSC Main: Counter 1
switching channel - main counter
• Counter 1 SSC Batch: Counter 1
switching channel - batch counter
• Counter 2 SSC Main: Counter 2
switching channel - main counter
• Counter 2 SSC Batch: Counter 2
switching channel - batch counter
• Counter 3 SSC Main: Counter 3
switching channel - main counter
• Counter 3 SSC Batch: Counter 3
switching channel - batch counter
• Counter 4 SSC Main: Counter 4
switching channel - main counter
• Counter 4 SSC Batch: Counter 4
switching channel - batch counter
rw
1
[output_state_com_lost] Fallback value if fieldbus connection is
lost
• State off: OFF
• State on: ON
• Keep last: keep last valid value
rw
1
1
Read and write; parameter can only be changed if no active connection to fieldbus controller
To configure the outputs of a port:
Requirements:
ü The parameter setting software has been started.
ü The detailed view of the device is active.
u Select the [io] > [port[n]] > [pin2] (n: 1...4) menu.
w The menu page shows the current settings of the digital output on pin 2 of the port.
u Set the parameters.
u Select menu [io] > [port[n]] > [pin4] (n: 1...4).
w The menu page shows the current settings of the digital output on pin 4 of the port.
u Set the parameters.
u Write the changed values to the device.
w The digital outputs of the device are configured.