AL4203 Remote I/O module 8DO 8DI
16
In the Two Point Mode switch point mode, the user can define a switch point (SP1) and a reset point
(SP2). As soon as the counter value increases and reaches SP1, the switching signal is set (ACTIVE).
As soon as the counter value decreases and reaches SP2, the switching signal is reset (INACTIVE).
1
0
SSC
1
2
0
1
SSC
SP1
SP2
Main
Batch
t
Fig.9: Two point mode (high-active)
1
0
SSC
1
2
0
1
SSC
SP1
SP2
Main
Batch
t
Fig.10: Two point mode (low-active)
A switching delay can be used to delay the setting of the switching signal. For the switching signal to
be set, the counter value must be greater than SP1 for at least as long as the set switching delay.
A reset delay can be used to delay the reset of the switching signals. For the switching signal to be
reset, the counter value must be less than SP2 for at least as long as the set reset delay.
0
1
SSC
1
0
SSC
1
2
SP1
SP2
Main
Batch
t
Fig.11: Two point mode (high-active) with switch delay (1)
and reset delay (2)
0
1
SSC
1
0
SSC
1
2
SP1
SP2
Main
Batch
t
Fig.12: Two point mode (low-active) with switch delay (1)
and reset delay (2)
The hysteresis function is not available.
4.7.5 Window mode
Can be combined with counter modules: CTUD, CTDIR
In the Window Mode switch point mode, the user can define two switch points (SP1, SP2 with SP1 >
SP2). The 2 switch points definte a range.
If the counter value is within the SP1...SP2 range, the switching signal is set (ACTIVE).
If the counter value is outside the SP1...SP2 range, the switching signal is reset (INACTIVE).
0
1
SSC
1 1
0
1
SSC
1
2
1
2
0
1
SSC
SP1
SP2
Main
Batch
t
Fig.13: Window mode (high active)
0
1
SSC
1 1
0
1
SSC
1
2
1
2
0
1
SSC
SP1
SP2
Main
Batch
t
Fig.14: Window mode (low active)
A switching delay can be used to delay the setting of the switching signal. For the switching signal to
be set, the counter value must be greater than SP1 for at least as long as the set switching delay.
A reset delay can be used to delay the reset of the switching signals. For the switching signal to be
reset, the counter value must be less than SP2 for at least as long as the set reset delay.