AL4143 Remote I/O module 16 DI
10
Maximum input frequency: 4500 Hz
Minimum detectable positive pulse width: 0.115 ms (+ positive edge)
Minimum detectable negative pulse width: 0.115 ms (+ negative edge)
4.4.1 Debouncing
The filter suppresses noise signals. The filter provides the input signals at the filter output with a delay
(debounce time). All signals shorter than the set debounce time are ignored by the filter.
Time diagram debounce filter:
2
1
1 11
0
1
0
1
0
1
t
Process data
Filter output
Filter input
1: Debounce time
2: Cycle time
4.4.2 Stretching
The filter stretches short input pulses. Level changes that occur during a stretching period are ignored.
The filter is configured via the following parameters:
Hold time: pulse duration to which short pulses are to be stretched. Pulses that are present for a
longer time than the hold time are not stretched.
Hold level: signal level to be stretched (HIGH or LOW)
Time diagram stretch filter (status HIGH):
2
1 1 1
0
1
0
1
0
1
t
Process data
Filter output
Filter input
1: Hold time
2: Cycle time
Time diagram stretch filter (status LOW):