AL4042 Remote I/O module 16 DI
32
Name Description Value range Access
[configuration] > [connection-
timeout]
Set timeout for interruption of the fieldbus
connection (value in milliseconds)
20: 2 ms
31000: 31000 ms
60000: 60000 ms
rw
1
[configuration] > [byteswap] Arrangement of the bytes in a data word big-endian: Big-endian format
little-endian: Little-endian
format
rw
1
1
Read and write
2
Read only
Requirements:
ü IoT Core Visualizer has been started.
ü The [Parameter] menu is active.
u Select the [Fieldbussetup] submenu.
w The menu page shows the current settings.
u Set the parameters.
u Click on to save the changes to the device.
u If necessary, restart the device.
w The ModbusTCP interface is configured.
9.2.3.2 Configuring input filters
u Observe the notes on input filters: Digital input filters (Ò/8)
Available parameters:
Name Description Value range Access
[pin2] > [debounce_time] Pin 2: debounce time (= value * 0.1milisec-
onds)
0: 0ms (default)
500: 50ms
rw
1
[pin2] > [hold_time] Pin 2: Hold time (= value * 0.1milliseconds) 0: 0ms (default)
60000: 6000 ms
rw
1
[pin2] > [hold_level] Pin 2: Hold level low: hold LOW
high: hold HIGH (default)
rw
1
[pin2] > [invert] Pin 2: Inversion signal not inverted: do not invert
(default)
signal inverted: invert
rw
1
[pin4] > [debounce_time] Pin 4: debounce time (= value * 0.1milisec-
onds)
0: 0ms (default)
500: 50ms
rw
1
[pin4] > [hold_time] Pin 4: Hold time (= value * 0.1milliseconds) 0: 0ms (default)
60000: 6000 ms
rw
1
[pin4] > [hold_level] Pin 4: Hold level low: hold LOW
high: hold HIGH (default)
rw
1
[pin4] > [invert] Pin 4: Inversion signal not inverted: do not invert
(default)
signal inverted: invert
rw
1
1
The parameter can only be changed if no connection to the fieldbus controller is active