IFM AL4033 handleiding
Handleiding
Je bekijkt pagina 12 van 61

AL4033 Remote I/O module 16 DI
12
• If the main counter reaches the threshold value CT (m = CT), the counter value is reset (m = 0).
Due to the overflow detection, the value of the batch counter is incremented (b = b+1).
• If the main counter falls below 0, the counter value is reset to the threshold value (m = CT-1). Due
to the underflow detection, the value of the batch counter is decremented (b = b-1).
• If the batch counter reaches the threshold value CTb (b = CTb), the counter value is reset (b = 0).
• If the batch counter falls below 0, the counter value is reset to the threshold value (b = CTb-1).
CTb
CT
0
0
t
Main Counter
Batch Counter
4.5.4 Counter mode CTDIR
In CTDIR (Count Direction) mode, the counter module operates either as an up counter with overflow
detection or as a down counter with underflow detection. The counting direction can be set.
Behaviour:
• The initial value of the main counter is m = 0. The initial value of the batch counter is b = 0. The
main counter has a threshold value CT. The batch counter has a threshold value CTb.
• The user can determine the counting direction. The counter module initially operates as an up
counter with overflow detection.
• If the counter module detects a positive edge at pin 4 of the port and the counting direction of the
port is set to “up”, the value of the main counter is incremented (m = m+1).
• If the main counter reaches the threshold value CT (m = CT), the counter value is reset (m = 0).
Due to the overflow detection, the value of the batch counter is incremented (b = b+1).
• If the batch counter reaches the threshold value CTb (b = CTb), the counter value is reset (b = 0).
• If the counter module detects a positive edge at pin 4 of the port and the counting direction at pin 2
of the port is set to “down”, the value of the main counter is decremented (m = m-1).
• If the main counter falls below 0, the counter value is reset to the threshold value (m = CT-1). Due
to the underflow detection, the value of the batch counter is decremented (b = b-1).
• If the batch counter falls below 0, the counter value is reset to the threshold value (b = CTb-1).
CTb
CT
0
0
t
Main Counter
Batch Counter
4.6 EtherCAT
• Device profile: Module device profile (EtherCAT slave)
• Supported protocols:
Bekijk gratis de handleiding van IFM AL4033, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
Merk | IFM |
Model | AL4033 |
Categorie | Niet gecategoriseerd |
Taal | Nederlands |
Grootte | 3248 MB |