AL4033 Remote I/O module 16 DI
10
4.4.4 Filter combination
The filters can be combined.
Example: All 3 filters are activated
Time diagram:
0
1
0
1
0
1
0
1
0
1
t
1
Digital input
Filter Debounce
Filter Hold
Filter Inverter
Process data
1: Cycle time
4.5 Counter
The device features one counter module per port.
A counter module consists of 2 separate counters:
• Main counter: The main counter counts the rising edges of the filtered digital input signals. The
main counter has a value range that is defined by a threshold value. If the value range of the main
counter is exceeded or not reached, an overflow or underflow signal is sent to the batch counter.
• Batch counter: The batch counter counts the overflow or underflow signals of the main counter.
Filter module pin 4
Filter module pin 2
Count input
Count input/
control input
Main counter
Batch counter
Process data
Process data
Counter module
A counter module can be operated in different operating modes. The following operating modes are
available.
Maximum count frequency: 4500 Hz
4.5.1 Counter mode CTU
In CTU (Count Up) mode, the counter module operates as an up counter with overflow detection and
overflow counter.
Behaviour:
• The initial value of the main counter is m = 0. The initial value of the batch counter is b = 0. The
main counter has a threshold value CT. The batch counter has a threshold value CTb.
• If the counter module detects a positive edge at pin 4 of the port, the value of the main counter is
incremented (m = m+1).