IO-Link input/output module AL2607
13
Parameter Index Subindex Value Increments Factory setting
Input invert X1.4 – 1 15103 9 0 [NO],
1 [YES]
- 0
Input invert X1.4 - 2 10
Input invert X1.5 - 1 11
Input invert X1.5 - 2 12
Input invert X1.6 - 1 13
Input invert X1.6 - 2 14
Input invert X1.7 - 1 15
Input invert X1.7 - 2 16
Subindex access: true
4.7.4 Combination of different input filters
The different input filters can be combined.
In the following example all 3 filters are used:
1
Filter hold
output
Inverter
output
IO-Link
process data
Digital input
Debouncing filter ‘
output
1: Cycle time
4.7.5 Analogue input signals
If the analogue input is activated, an average over the time specified in the parameter is calculated.
1
t
Digital input
IO-Link process data
1: time period for averaging
Parameter Index Subindex Value (ms) Increments Factory setting
Analog Input filter X1.0 15104 1 1 – 100 1 10
Analog Input filter X1.1 3
Analog Input filter X1.2 5
Analog Input filter X1.3 7