7 Operating and display elements
X1.4
X1.2
X1.6
X1.0
X1 X31
X1.5
X1.3
X1.7
X1.1
1
2
3
4
5
6
7
6
7
6
7
6
7
6
7
6
7
6
7
6
7
8
9
1: LED INT Internal error
2: LED 1 Port group 1 error
3: LED 2 Port group 2 error
4: LED UA Supply voltage ports
5: - Not used
6: LED I/O2 Status input/output I/O2
7: LED I/O1 Status input/output I/O1
8:
LED
IO-Link communication
9: LED US Supply voltage
7.1 LEDs
LED Colour
Input/output func-
tion
Status Designation
INT Red On Internal error
Off No internal error
Device in operating mode
1 Red On Short circuit in port group 1 or undervoltage UA
Off No error in port group 1
Device in operating mode
2 Red On Short circuit in port group 2 or undervoltage UA
Off No error in port group 2
Device in operating mode
US Green On Voltage supply ≥ 18 V
Off Voltage supply < 16 V
UA Green On Voltage supply ≥ 18 V
Off Voltage supply < 16 V
Green On IO-Link communication active
Off IO-Link communication not active
I/O1, I/O2 Yellow Digital input On Input signal High
Off Input signal Low
Flashing Short circuit
Digital output On Output signal High
Off Output signal Low
Flashing Short circuit
Analogue input On Signal within measuring range
Off Signal outside measuring range
Flashing Short circuit