9
4 Function
4.1 IO-Link
The device offers the following IO-Link functions:
IO-Link master (IO-Link revision 1.0 and 1.1)
8 IO-Link ports (Class A) for connecting IO-Link devices
4.1.1 IO-Link supply
The device offers supplies for 8 IO-Link devices (sensors, actuators).
Ports X01...X08 are class A ports.
The device ensures fire protection for connected IO-Link devices by providing an energy-limited circuit
at the ports (according to IEC61010-1 and class 2 to UL1310).
4.2 Parameter setting
The device can be configured with the following options:
Parameter setting software
ifm moneo OS + ifm moneo|configure
ifm moneo|configure free
ifm IoT Core
ifm IoT Core Visualizer
EtherNet/IP
Projection software
4.3 EtherNet/IP
The device supports supports the following EtherNet/IP functions:
Device profile: EtherNet/IP device
2-port switch for access to the fieldbus interface
Min. cycle time: 1ms (RPI)
Supported connection classes: 1, 3
Supported connection types:
Exclusive Owner
Input Only
Listen Only
UCMM support
Predefined fieldbus objects
Identity Object (0x01)
Message Router Object (0x02)
Assembly Object (0x04)
Connection Manager (0x06)