AL1921 IO-Link master with EtherNet/IP interface
28
Parameter Description Value range Access
Fail-safe digital out Fail-safe value of the output
for operating mode "digital
output (DO)"
• Reset: default value
• Old: most recent process value
• Set: HIGH level
rw
1
2
Fail-safe IO-Link Fail-safe value of the output
for "IO-Link" operating mode
• Off: Fail-safe deactivated
• Reset: Fail-safe activated – default value
• Old: Fail-safe activated – most recent process
value
• Pattern: Fail-safe activated - byte sequence
rw
1
2
1
Read and write
2
Read and write; parameter can only be changed if no active connection to fieldbus controller
Requirements:
ü The parameter setting software has been started.
ü The connection to the device has been established.
ü The detailed view of the device is active.
ü Configuration mode “Independent” is enabled.
u Select the [Port x] (x = 1…8) menu.
w The menu page shows the current settings.
u Setting fail-safe values
u Write the changed values to the device.
w Fail-safe values are configured.
9.1.13 Ports: Setting data transmission to the monitoring software
Available parameters:
Name Description Value range Access
Transmission to moneo, LR
Agent or SMARTOBSERVER
Enable / Disable the transmis-
sion of process data of the port
to the monitoring software
• Disabled: Process data is not transmitted
• Enabled: Process data is transmitted
rw
1
1
Read and write
To set the data transmission:
Requirements:
ü The parameter setting software has been started.
ü The connection to the device has been established.
ü The detailed view of the device is active.
ü Interface to the monitoring software has been configured.
u Select the [Port x] (x = 1…8) menu.
w The menu page shows the current settings.
u Set the parameters.
u Write the changed values to the device.
w Data transmission to the monitoring software has been set.
9.1.14 Info: Reading device information
Available information: