IFM AL1921 handleiding

135 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 28 van 135
AL1921 IO-Link master with EtherNet/IP interface
28
Parameter Description Value range Access
Fail-safe digital out Fail-safe value of the output
for operating mode "digital
output (DO)"
Reset: default value
Old: most recent process value
Set: HIGH level
rw
1
2
Fail-safe IO-Link Fail-safe value of the output
for "IO-Link" operating mode
Off: Fail-safe deactivated
Reset: Fail-safe activated – default value
Old: Fail-safe activated – most recent process
value
Pattern: Fail-safe activated - byte sequence
rw
1
2
1
Read and write
2
Read and write; parameter can only be changed if no active connection to fieldbus controller
Requirements:
ü The parameter setting software has been started.
ü The connection to the device has been established.
ü The detailed view of the device is active.
ü Configuration mode “Independent” is enabled.
u Select the [Port x] (x = 1…8) menu.
w The menu page shows the current settings.
u Setting fail-safe values
u Write the changed values to the device.
w Fail-safe values are configured.
9.1.13 Ports: Setting data transmission to the monitoring software
Available parameters:
Name Description Value range Access
Transmission to moneo, LR
Agent or SMARTOBSERVER
Enable / Disable the transmis-
sion of process data of the port
to the monitoring software
Disabled: Process data is not transmitted
Enabled: Process data is transmitted
rw
1
1
Read and write
To set the data transmission:
Requirements:
ü The parameter setting software has been started.
ü The connection to the device has been established.
ü The detailed view of the device is active.
ü Interface to the monitoring software has been configured.
u Select the [Port x] (x = 1…8) menu.
w The menu page shows the current settings.
u Set the parameters.
u Write the changed values to the device.
w Data transmission to the monitoring software has been set.
9.1.14 Info: Reading device information
Available information:

Bekijk gratis de handleiding van IFM AL1921, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkIFM
ModelAL1921
CategorieNiet gecategoriseerd
TaalNederlands
Grootte11184 MB