AL1921 IO-Link master with EtherNet/IP interface
112
11.2.3.2 Acyclic commands
Set Mode (0x10)
The command changes the operating mode of an IO-Link port of the device.
Command request
Byte
(offset)
Bit
7 6 5 4 3 2 1 0
4 Port No. (LSB)
5 Port No. (MSB)
6 reserved
7 reserved
8 reserved
9 reserved
10 Trigger 0x10
11 Target Mode
12 reserved
45 reserved
Legend:
Port No. IO-Link Port
Port No. 0x1234
Port No. (MSB): 0x12
Port No. (LSB): 0x34
1WORD 0x0001: Port 1
0x0002: Port 2
0x0003: Port 3
0x0004: Port 4
0x0005: Port 5
0x0006: Port 6
0x0007: Port 7
0x0008: Port 8
Trigger Control of the command execution 1BIT 0x0: no action
0x1: Execute command
Target Mode Operating mode of the IO-Link port 1BYTE 0x00: deactivated
0x01: Digital input (DI)
0x02: Digital output (DO)
0x03: IO-Link