IFM AL1921 handleiding

135 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 105 van 135
IO-Link master with EtherNet/IP interface AL1921
105
11.2.2.4 Output Assembly (Instance 150)
Byte
(Offset)
Bit
7 6 5 4 3 2 1 0
0…1
Digital Output (Ò Mapping: Digital output/106)
2…3 reserved
4…45
Acyclic Command Channel: Request (Ò Request channel/108)
46 Port X01: Output Data IO-Link (n Bytes)
1
46+n Port X02: Output Data IO-Link (n Bytes)
1
46+2n Port X03: Output Data IO-Link (n Bytes)
1
46+3n Port X04: Output Data IO-Link (n Bytes)
1
46+4n Port X05: Output Data IO-Link (n Bytes)
1
46+5n Port X06: Output Data IO-Link (n Bytes)
1
46+6n Port X07: Output Data IO-Link (n Bytes)
1
46+7n Port X08: Output Data IO-Link (n Bytes)
1
1
n: {2, 4, 8, 16, 32}; n is determined by the parameter [Port Process Data Size] in the configuration assembly (Ò
Configuration Assembly (Instance 199)/95)
11.2.2.5 Output Assembly (Instance 151)
Byte
(Offset)
Bit
7 6 5 4 3 2 1 0
0…1
Digital Output (Ò Mapping: Digital output/106)
2 Port X01: Output Data IO-Link (n Bytes)
1
2+n Port X02: Output Data IO-Link (n Bytes)
1
2+2n Port X03: Output Data IO-Link (n Bytes)
1
2+3n Port X04: Output Data IO-Link (n Bytes)
1
2+4n Port X05: Output Data IO-Link (n Bytes)
1
2+5n Port X06: Output Data IO-Link (n Bytes)
1
2+6n Port X07: Output Data IO-Link (n Bytes)
1
2+7n Port X08: Output Data IO-Link (n Bytes)
1
1
n: {2, 4, 8, 16, 32}; n is determined by the parameter [Port Process Data Size] in the configuration assembly (Ò
Configuration Assembly (Instance 199)/95)

Bekijk gratis de handleiding van IFM AL1921, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkIFM
ModelAL1921
CategorieNiet gecategoriseerd
TaalNederlands
Grootte11184 MB