IFM AL1327 handleiding
Handleiding
Je bekijkt pagina 49 van 125

IO-Link master with EtherNet/IP interface AL1327
49
{
"code":"request",
"cid":-1,
"adr":"/iolinkmaster/port[1]/datastorage/chunksize/getdata"
}
Example: s = 256
u Start writing the data storage string segment by segment ("size" = size of the read data storage)
{
"code":"request",
"cid":-1,
"adr":"/iolinkmaster/port[1]/datastorage/start_stream_set",
"data": {"size": n}
}
Example: size = 550
u Transmit data storage string segment by segment ("value" = string value with length s)
{
"code":"request",
"cid":-1,
"adr":"/iolinkmaster/port[1]/datastorage/stream_set",
"data": {"value": "aWZtfgIAAABBTDF4NXhfY25faXRfdDIuMi43Nw..."
}
9.2.13 Ports: Setting data transmission to the monitoring software
Substructure: iolinkmaster/port[x] (x: 1…8)
Available data points:
Name Description Value range Access
../senddatatosmob Enable / Disable the transmission of pro-
cess data of the port to the monitoring
software
• 0: Disabled – process data will not be
transmitted
• 1: Enabled – process data will be
transmitted
rw
1
1
Read and write
9.2.14 Ports: Reading / writing process data
Substructure: iolinkmaster/port[x] (x: 1…8)
Available data points:
Name Description Value range Access
../pin2in Digital input (pin 2) • 0: OFF
• 1: ON
ro
1
../iolinkdevice/pdin Input data (pin4) "DI" operating mode:
• 0x00: OFF
• 0x01: ON
"IO-Link" operating mode:
• Process value in hexadecimal representation
ro
1