IFM AL1327 handleiding

125 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 46 van 125
AL1327 IO-Link master with EtherNet/IP interface
46
9.2.11 Ports: Setting the operating mode Pin 4 (US)
Pin 4 of ports X01...X08 supports the following operating modes:
Disabled: No data transmission at pin 4 (C/Q) of the port
Digital input: Binary input signal at pin 4 (C/Q) of the port
Digital output Binary output signal at pin 4 (C/Q) of the port
IO-Link: IO-Link data transmission via pin 4 (C/Q) of the port
The set operating mode must match the operating mode of the device connected to the port (sensor,
actuator, IO-Link device).
Substructure: iolinkmaster/port[x] (x: 1…8)
Available data points:
Name Description Value range Access
…/mode Operating mode of pin 4 (US) of the
port
0: Disabled - port deactivated
1: DI - digital input
2: DO - digital output
3: IO-Link - IO-Link data
rw
1
2
../mastercycletime_actual Current cycle time of the data trans-
fer between port and IO-Link device
(value in µs)
0: best possible cycle time
1: 1 µs
132800: 132800 µs
ro
3
../comspeed Current transfer rate between port
and IO-Link device
0: COM1 - 4.8 kBaud
1: COM2 - 38.4 kBaud
2: COM3 - 230.4 kBaud
ro
3
../mastercycletime_preset Cycle time of the data transfer be-
tween port and IO-Link device (val-
ue in µs); only in IO-Link operating
mode
0: Automatically set the best possible cycle
time
1: 1 µs
132800: 132800µs
rw
1
2
1
Read and write
2
The parameter can only be changed if no connection to the fieldbus controller is active
3
Read only
9.2.12 Ports: Configuring device validation and data storage
The device supports the functions device validation and backup / restore of parameter data of the
connected IO-Link devices.
The following options are available:
Option
Validation of the connected
IO-Link device
Backup of parameter values
Restore of parameter val-
ues
[No check and clear] No No No
[Type compatible V1.0 de-
vice]
Yes, test compatibility with IO-
Link standard V1.0
No No
[Type compatible V1.1 de-
vice]
Yes, test compatibility with IO-
Link standard V1.1
No No
[Type compatible V1.1 de-
vice with Backup + Restore]
Yes, test compatibility with IO-
Link standard V1.1 and identity
of design (vendor ID, device
ID)
Yes, automatic backup of pa-
rameter values; Changes to
the current parameter values
will be stored
Yes, restore of parameter val-
ues when connecting an iden-
tical IO-Link device with facto-
ry settings
[Type compatible V1.1 de-
vice with Restore]
Yes, test compatibility with IO-
Link standard V1.1 and identity
of design (vendor ID, device
ID)
No, there is no automatic
backup; Changes to the pa-
rameter values are not stored
Yes, restore of parameter val-
ues when connecting an iden-
tical IO-Link device with facto-
ry settings

Bekijk gratis de handleiding van IFM AL1327, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkIFM
ModelAL1327
CategorieNiet gecategoriseerd
TaalNederlands
Grootte10357 MB