IO-Link master with EtherNet/IP interface AL1327
27
ü Operating mode of pin 4 of the port is "IO-Link".
u Select the [Port x] > [IO-Link] menu (x = 1…8).
u Set the cycle time.
u Write the changed values to the device.
w Cycle time of the IO-Link port is set.
9.1.12 Ports: Setting fail-safe values
The user can set the fail-safe values of the outputs of the IO-Link ports for the "Independent"
configuration mode. The fail-safe values will only be enabled if the EtherNet/IP connection is
interrupted.
Available parameters:
Parameter Description Value range Access
Fail-safe digital out Fail-safe value of the output
for operating mode "digital
output (DO)"
Reset: default value
Old: most recent process value
Set: HIGH level
rw
1
2
Fail-safe IO-Link Fail-safe value of the output
for "IO-Link" operating mode
Off: Fail-safe deactivated
Reset: Fail-safe activated – default value
Old: Fail-safe activated – most recent process
value
Pattern: Fail-safe activated - byte sequence
rw
1
2
1
Read and write
2
The parameter can only be changed if no connection to the fieldbus controller is active
Requirements:
ü The parameter setting software has been started.
ü The connection to the device has been established.
ü The detailed view of the device is active.
ü Configuration mode “Independent” is enabled.
u Select the [Port x] (x = 1…8) menu.
w The menu page shows the current settings.
u Setting fail-safe values
u Write the changed values to the device.
w Fail-safe values are configured.
9.1.13 Ports: Setting data transmission to the monitoring software
Available parameters:
Name Description Value range Access
Transmission to moneo, LR
Agent or SMARTOBSERVER
Enable / Disable the transmis-
sion of process data of the port
to the monitoring software
Disabled: Process data is not transmitted
Enabled: Process data is transmitted
rw
1
1
Read and write
To set the data transmission:
Requirements:
ü The parameter setting software has been started.
ü The connection to the device has been established.
ü The detailed view of the device is active.