IO-Link master with EtherNet/IP interface AL1325
39
9.2.3.4 Example: Read multiple elements sequentially
Task: The following current values of the device are to be read consecutively: temperature, serial
number
Solution: Read the current parameter values using the service getdatamulti (data point
temperature: /processdatamaster/temperature ; data point serial number: /deviceinfo/
serialnumber )
Request:
{
"code":"request",
"cid":4711,
"adr":"/getdatamulti",
"data":{"datatosend":[
"/processdatamaster/temperature",
"/deviceinfo/serialnumber"]
}
}
Response:
{
"cid":4711,
"data":{
"processdatamaster/temperature":{
"code":200,
"data":44
},
"deviceinfo/serialnumber":{
"code":200,
"data":"000174210147"
}
},
"code":200
}