IFM AL1325 handleiding
Handleiding
Je bekijkt pagina 39 van 121

IO-Link master with EtherNet/IP interface AL1325
39
9.2.3.4 Example: Read multiple elements sequentially
Task: The following current values of the device are to be read consecutively: temperature, serial
number
Solution: Read the current parameter values using the service getdatamulti (data point
temperature: /processdatamaster/temperature ; data point serial number: /deviceinfo/
serialnumber )
Request:
{
"code":"request",
"cid":4711,
"adr":"/getdatamulti",
"data":{"datatosend":[
"/processdatamaster/temperature",
"/deviceinfo/serialnumber"]
}
}
Response:
{
"cid":4711,
"data":{
"processdatamaster/temperature":{
"code":200,
"data":44
},
"deviceinfo/serialnumber":{
"code":200,
"data":"000174210147"
}
},
"code":200
}
Bekijk gratis de handleiding van IFM AL1325, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
| Merk | IFM |
| Model | AL1325 |
| Categorie | Niet gecategoriseerd |
| Taal | Nederlands |
| Grootte | 9966 MB |







