Je bekijkt pagina 14 van 121
AL1325 IO-Link master with EtherNet/IP interface
14
u Tighten the cable plug using 1.3 ± 0.1Nm.
6.5.2 Connecting IO-Link devices (Class B)
Wiring information:
The connection of IO-Link devices (Class B) requires the supply with an additional auxiliary voltage
UA. Feeding is done with the help of a Y-connection cable (Ò accessories).
CAUTION
Non-compliance with the electrical separation of the circuits
w Risk of fire
u Ensure that the external supply UA is electrically separated from the power circuit of the
unit by basic insulation (according to IEC 61010-1, secondary current circuit with max.
30 V DC, derived from mains circuit up to 300 V of overvoltage category II).
u Ensure that the IO-Link devices and the connection technology support the electrical
separation.
When connecting an IO-Link device (Class B), the additional digital input at pin 2 of the port is not
available.
u IO-Link Devices über Y-Verbindungskabel mit Ports X01...X04 verbinden.
u Connect Y cabes to the supplyvoltage 24VDC (20…30 V SELV/PELV)
u For connection, use M12 connectors (minimum protection rating: IP 65 / IP 66 / IP 67 / IP 69K).
u Tighten the cable plug using 1.3 ± 0.1Nm.
6.6 Ground connection
The FE potential is connected to the following points of the device:
Upper mounting lug of the housing
To ensure the protection of the device against electrical interference and to ensure the safe
function of the device, the housing has to be connected to the GND of the installation using the
shortest possible route.
u Ground the device via the mounting screw of the upper mounting lug.
6.7 Voltage supply
The device is connected to the US supply voltage via the Power IN port.
The US supply voltage supplies the device and the sensors connected to the ports X01...X04 with
voltage.
Wiring:
43
2 1
1: +24VDC (US)
2: not used
3: GND (US)
4: not used
u Disconnect power.
u Connect the device via port X31 to 24VDC (20…30V SELV/PELV; according to IEC 61010-1,
secondary circuit with max. 30 V DC, supplied from main circuit up to 300 V of overvoltage
category).
u For connection, use an L-coded M12 connector (minimum protection rating: IP 65 / IP 66 / IP 67 /
IP 69K).