AL1304 IO-Link master with PROFINET interface
8
4 Function
4.1 IO-Link
The device offers the following IO-Link functions:
IO-Link master (IO-Link revision 1.0 and 1.1)
4 IO-Link ports (Class A) for connecting IO-Link devices
4.1.1 IO-Link supply
The device offers supplies for 4 IO-Link devices (sensors, actuators).
Ports X01...X04 are class A ports.
The device ensures fire protection for connected IO-Link devices by providing an energy-limited circuit
at the ports (according to IEC61010-1 and class 2 to UL1310).
4.2 Parameter setting
The device can be configured with the following options:
Parameter setting software
ifm moneo OS + ifm moneo|configure
ifm moneo|configure SA
ifm IoT Core
REST API
ifm IoT Core Visualizer
PROFINET
Projection software
4.3 Visual indication
The device displays the following indications:
Status and error indication of the PROFINET gateway and the system
Status of the voltage supply US
Status and activity indication of the Ethernet connections
Status of the MQTT connection
Status and error indication of the IO-Link ports (class A)
4.4 PROFINET
Supported PROFINET functions:
Device profile: PROFINET RT device (Conformance Class C)
2-port switch for access to the PROFINET interface; integrated switch complies with RT and IRT
according to PROFINET V2.3
Supported protocols: SNMP, LLDP, MRP, DCP, RTA, RTC Class 1 (not synchronised)