Electrical connection
Disconnect the installation from power. Connect the unit as indi-
cated on the terminals. Never connect the minus potentials to
each other or the minus potentials to the FE connection. Ensure
an electrically save ground connection between AS-i controller
e
(terminal FE) and ground of the unit.
Supply the controller
e
with a 24V DC voltage (20 ... 30V PELV), e.g.
from the 24V power supply DN2011 of ifm electronic. The connection
is made to the terminals +24V and 0V.
Operating and indicating elements
Information concerning the state of the master (AC1305)/masters
/AC1306) and the connected system is given via three diagnostic LEDs
on the controller
e
.
• LED PWR/COM lights: AS-i voltage present, at least one slave
was detected
• LED PWR/COM flashes: AS-i voltage present, but no slave was
detected correctly
• LED PROJ lights: Projection mode active, the configuration
monitoring is deactivated
• LED PROJ flashes: Projection mode active, changeover to
protected mode not possible as a slave
with the address 0 is connected
• LED CONF/PF lights: Projected and current configuration do
not match
• LED CONF/PF flashes: Periphery fault on at least one connected
slave
Ethernet Status LEDs
• LED address state:
green flashing 1Hz: The IP address is freely selectable
red flashing 1Hz: invalid MAC ID (internal fault
Ethernet interface)
red flashing 2Hz: no valid Ethernet configuration
loaded
PAGE 10