Handleiding
Je bekijkt pagina 36 van 39

METHODOLOGY FOR COOLING CAPACITY TEST SETTING
Full load and half load capacity test modes are applicable only for testing purpose in
authorized test laboratories. Before setting the mode, lab conditions to be stabilized as per
IS1391 Part 2.
Full Load (100%) Capacity settings:
Step 1: By using remote controller turn ON the unit .
Step 2: Set Cool mode at 30όC set temperature and Fan speed medium.
Step 3: Press Sleep button continuously for 7 times within 10 sec.
Step 4: IDU will beep thrice.
Step 5: Change the set temp to 25όC.
Step 6: Full load test setting will be activated & IDU display will show ” FL ”.
Half Load (50%) Capacity settings:
Step 1: By using remote controller turn ON the unit .
Step 2: Set Cool mode at 30όC set temperature and Fan speed medium.
Step 3: Press Sleep button continuously for 7 times within 10 sec.
Step 4: IDU will beep thrice.
Step 5: Change the set temp to 26όC.
Step 6:
Full load test setting will be activated & IDU display will show ” HL ”.
NOTE:
During cooling capacity test vertical louver should be in straight position.
32
35
Bekijk gratis de handleiding van IFB CI183GN22RGN1, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
| Merk | IFB |
| Model | CI183GN22RGN1 |
| Categorie | Airco |
| Taal | Nederlands |
| Grootte | 5157 MB |







