Alarm
ID
Alarm
Name
Alarm
Severity
Possible Causes Troubleshooting
2039 Output
overcurre
nt
Major Cause ID = 1
The power grid
voltage drops
dramatically or the
power grid is short-
circuited. As a
result, the inverter
transient output
current exceeds the
upper threshold,
and protection is
triggered.
1. The inverter monitors its external
operating conditions in real time and
automatically recovers after the fault
is rectied.
2. If the alarm persists and aects the
energy yield of the PV plant, check
whether the output is short-circuited.
If the fault cannot be
rectied,
contact your dealer or Huawei
technical support.
2040 Output
DC
compone
nt
overhigh
Major Cause ID = 1
The DC component
of the inverter
output current
exceeds the upper
threshold.
1. The inverter monitors its external
operating conditions in real time and
automatically recovers after the fault
is rectied.
2. If the alarm persists and aects the
energy yield of the PV plant, contact
your dealer or Huawei technical
support.
2051 Abnorma
l residual
current
Major Cause ID = 1
The insulation
impedance of the
input side to PE
decreases when the
inverter is
operating.
1. If the alarm occurs accidentally, the
external power cable may be
abnormal temporarily. The inverter
automatically recovers after the fault
is rectied.
2. If the alarm persists or lasts a long
time, check whether the impedance
between the PV string and ground is
too low.
SUN2000-(12KTL-25KTL)-M5 Series
User Manual 8 Maintenance
Issue 01 (2022-06-15) Copyright © Huawei Digital Power Technologies Co., Ltd. 62