Parameter Name Description
High feed-in power duration threshold for
triggering inverter shutdown (s)
The default value is 20. This
parameter species the duration
threshold of high feed-in power for
triggering inverter shutdown.
● When High feed-in power
duration threshold for triggering
inverter shutdown is set to 5,
Shutdown at high feed-in power
takes precedence.
● When High feed-in power
duration threshold for triggering
inverter shutdown is set to 20,
Grid connection with limited
power takes precedence (when
Active power control is set to
Grid connection with limited
power).
Note a: This parameter is supported only for the AS4777 grid code.
----End
7.2.1.2 Apparent Power Control on the Inverter Output Side
On the home screen, tap Settings > Power adjustment to set inverter
parameters.
Figure 7-8 Apparent power control
SUN2000-(12KTL-25KTL)-M5 Series
User Manual 7 Man-Machine Interactions
Issue 01 (2022-06-15) Copyright © Huawei Digital Power Technologies Co., Ltd. 53